Microchannel Optimization for Direct Refrigerant Cooling of EV Batteries

The performance and safety of an electric vehicle depend strongly on its battery temperature window. Lithium-ion cells, which are still the dominant energy-storage units in modern EVs, suffer from accelerated aging when they are exposed to high temperature, and they also lose power capability under low-temperature operation. The recommended operating window for most Li-ion chemistries is approximately 15 °C to 35 °C, while the maximum temperature difference inside the pack should be kept below 5 °C to maintain balanced electrochemical reactions and to avoid localized degradation or thermal runaway. In this context, battery thermal management is not an accessory function but a core component in EV engineering. Several cooling architectures are used in production EVs: air cooling, liquid cooling, phase-change-material cooling, and refrigerant-based direct cooling. Among them, direct cooling is attractive because the refrigerant evaporator plate is placed directly beneath the battery modules, so the heat generated by the cells is absorbed by the two-phase refrigerant without the intermediate coolant loop. This removes the chiller, the pump, the secondary coolant, and the associated piping, thereby reducing the system mass and improving the effective temperature difference between the heat source and the cold fluid.

Direct cooling has been used in series-production electric vehicles since the early 2010s, and its application range has spread rapidly as fast charging, high discharge rates, and high energy-density cells impose stronger cooling demands. The heat transfer performance of a direct-refrigerant cold plate is not determined only by the compressor, condenser, and expansion valve; the internal structure of the cold plate has a decisive influence on how the refrigerant boils and how the resulting two-phase flow pattern distributes along the channel. A well-designed microchannel layout can greatly enlarge the wetted heat-transfer area, promote nucleate boiling, stabilize the liquid film, and improve the temperature uniformity of the battery plate. Because of that, the combination of direct cooling and microchannel heat exchangers is regarded as a promising route for EV battery thermal management.

Although numerical simulations provide useful insights into microchannel heat transfer, they often fail to reproduce the complex phase-change mechanisms involving bubble nucleation, bubble growth, coalescence, interfacial oscillation, dry-out, and reverse flow. Experimental visualization is therefore essential to observe how the refrigerant really behaves inside the channel. In this study, I built a fully instrumented direct-cooling experimental loop with a transparent visualization section so that the flow boiling phenomena could be recorded simultaneously with the thermal measurements. The study was carried out in two main steps. In the first step, I compared a micro-scale cold plate, whose channel hydraulic diameter was exactly 3 mm, with two conventional-scale cold plates whose channel widths were 4 mm and 5 mm. In the second step, I investigated two additional smaller microchannel widths of 1 mm and 2 mm so that the effect of channel miniaturization on boiling heat transfer could be isolated under the same channel height, wall spacing, length, and operating-environment conditions. Throughout the entire research, I emphasized the dynamic cooling process rather than a steady-state snapshot. This approach can help engineers understand not only how much heat can be removed by a given microchannel cold plate but also how quickly the cooling response develops when the compressor speed, expansion-valve opening, or battery heat-generation rate changes.

Experimental Platform and Instrumentation

Refrigerant Direct-Cooling System

I designed a laboratory-scale direct-cooling system whose architecture is analogous to a vehicle refrigeration circuit but contains only one evaporator, i.e. the microchannel cold plate. The refrigerant is R134a, and the compressor is a hermetically sealed reciprocating type with a displacement of 3.5 cm³ and a nominal capacity of approximately 480 W. The condenser is a fin-and-tube air-cooled heat exchanger rated at 700 W. A compact H-type electronic expansion valve is used as the throttling device; its opening is regulated digitally so that I could change the operating condition in a repeatable manner. Four-way and shut-off valves allow the circuit to be switched between cooling and heating functions if needed, although only the cooling mode is treated in this work. A filter–dryer is installed in the liquid line, and a sight glass helps to inspect the refrigerant phase before it reaches the expansion valve. The main components and functions are summarized in table 1.

Table 1 Main components of the direct-cooling experimental loop.
Component Type/design Specification
Compressor Hermetic reciprocating Displacement 3.5 cc; capacity ~480 W
Condenser Fin-and-tube, air-cooled 275 mm × 150 mm × 45 mm; nominal capacity 700 W
Expansion valve Electronic expansion valve (H-type) Max differential pressure 3.5 MPa; capacity ~0.9 kW
Cold plate Aluminium, CNC-machined parallel microchannels Machining accuracy ±0.005 mm
Heater Copper heating block with two cartridge heaters Total heating power up to 230 W
Surrogate battery Aluminium block between heater and cold plate Simulates heat generation and thermal mass of an EV battery module

The most important part of the experimental platform is the visualization cold-plate section. The cold plate itself is machined from a solid aluminium billet, and the parallel microchannels are open on the upper side. The upper side is closed by an acrylic glass window, which allows a high-speed camera to observe the refrigerant flow pattern directly. A steel cover frame is used to apply a uniform clamping force. Silicone–rubber gaskets are inserted between the cover frame, acrylic plate, and aluminium body to guarantee sealing without overstressing the transparent part. Underneath the cold plate, an aluminium surrogate-battery block has three thermocouple holes drilled in the longitudinal direction, and a copper heating block is installed below it. The entire stack is wrapped with thick thermal insulation to reduce heat leakage. The microchannel test section is therefore a transparent direct-evaporator simulator that replicates the thermal interaction between an EV battery pack and the refrigerant in a realistic manner.

Measurement and Data-Acquisition System

To obtain reliable transient data, temperature, pressure, flow rate, and flow-pattern signals are recorded synchronously. K-type probe thermocouples are inserted in the cold plate, the surrogate battery, and the heating block. PT100 temperature/pressure transmitters are located at the inlet and outlet of the cold plate to give the refrigerant state. A micro oval-gear flowmeter with a range of 0–800 mL/min is installed in the liquid line to measure the volumetric flow of refrigerant. The transparency window permits a high-speed digital camera to monitor the boiling flow. Table 2 reports the relevant measurement ranges and accuracies.

Table 2 Measuring devices used in the direct-cooling experiments.
Measured variable Instrument Range / description Accuracy
Temperature of cold plate and battery surrogate K-type probe thermocouple −40 to 260 °C ±0.01 °C
Refrigerant temperature PT100 temperature/pressure transmitter −40 to 80 °C 0.1%
Pressure PT100 pressure transmitter −0.1 to 2 MPa 0.1%
Volumetric flow rate Micro oval-gear flowmeter 0–800 mL/min 1%
Flow pattern High-speed camera 2320 × 1720 pixels; 100 FPS at full frame —

The analogue signals from the transmitters are first converted to digital values by intelligent panel meters with a Modbus/RS485 interface. A MATLAB serial-communication program was developed to read all of the converted values at a constant time interval, synchronize the time stamp, and store the data in a structured file. The temperature data from the discrete thermocouple channels are recorded by a separate multi-point data logger. The whole acquisition system is triggered before the heater is powered, so the initial heat-up transient and the subsequent direct-cooling transient are both captured.

Design of the Investigated Microchannel Geometries

The design of the cold-plate channels follows the single-variable principle so that the comparison between different plates is meaningful. All cold plates have the same channel height of 3 mm, the same interval wall thickness of 2 mm, and the same channel length of 80 mm. The only geometric variable is the channel width. Starting from a baseline width of 3 mm, which corresponds to a hydraulic diameter of 3.0 mm and is therefore located on the conventional boundary between micro and macro channels, I expanded the width to 4 mm and 5 mm for comparison with conventional-scale channels, and reduced it to 2 mm and 1 mm for comparison with finer microchannels. The resulting hydraulic diameter is calculated as

$$D_h = \frac{2WH}{W+H} $$

where \(W\) is the width and \(H\) is the height of the rectangular channel. For the five plates used in this investigation, the hydraulic diameters are listed in table 3. The volume flow rate, heat flux, and heat-transfer coefficient are all evaluated per unit of the wetted channel area, so the geometric comparison is consistent.

Table 3 Geometric parameters of the five cold-plate channel variants.
Channel label Width \(W\) (mm) Height \(H\) (mm) Hydraulic diameter \(D_h\) (mm) Rib thickness (mm) Channel length (mm)
Microchannel 1 1 3 1.50 2 80
Microchannel 2 2 3 2.40 2 80
Reference channel 3 3 3.00 2 80
Conventional channel 1 4 3 3.43 2 80
Conventional channel 2 5 3 3.75 2 80

Refrigerant Charge and Experimental Procedure

Finding the correct refrigerant charge is essential for obtaining meaningful and comparable results. During charging, the circuit was first evacuated by a vacuum pump. After confirming that the system held the vacuum, R134a was gradually introduced until the pressure reached approximately 5–6 bar. The compressor was then started, and the charge was fine-tuned by observing the low-side pressure. For the experiments, the target saturation temperature was roughly −5 °C, corresponding to an absolute saturation pressure of about 2.43 bar for R134a. After repeated adjustment, the system was charged with 320 g of R134a. This charge quantity was then kept unchanged for every test, regardless of which cold plate was being investigated.

In every dynamic direct-cooling test, the EV battery surrogate is first heated by the electric cartridges. When the central temperature of the surrogate battery reaches 40 °C, the compressor is switched on and data acquisition is started. The system runs for 900 s so that the surrogate cell temperature and refrigerant state can reach a quasi-steady level. After the test, the compressor is stopped, the heater is turned off, and the system is allowed to recover to the ambient condition before the next test begins. All tests were performed in a controlled laboratory room at an air temperature of 25.5 °C and an atmospheric pressure of about 1003 hPa. The high-speed camera was mounted above the transparent window before each run, and the light intensity as well as the focus were adjusted so that the whole channel width could be observed clearly.

Data Reduction

The measured volume flow \(\dot V\) is transformed into a mass flux by

$$G=\frac{\rho \dot V}{N A_c}$$

where \(\rho\) is the liquid density at the flowmeter, \(N\) is the number of parallel microchannels, and \(A_c=WH\) is the cross-sectional area of a single channel. The local wall heat flux is obtained from a one-dimensional steady conduction assumption because the heat-conduction path from the heating block to the cold-plate wall is short and well insulated. The heat flux is written as

$$q = \lambda_{Al}\frac{T-T_w}{\delta}$$

where \(\lambda_{Al}\) is the thermal conductivity of aluminium, \(T\) is the temperature measured in the thermocouple hole below the channel, \(T_w\) is the temperature of the microchannel inner wall, and \(\delta\) is the distance between that thermocouple hole and the wall. Since the resistance of the aluminium blocks between the cell-center temperature and the cold-plate measuring point is also in the same conduction path, the wall temperature can be inferred from

$$T_w = T – \frac{\delta}{\delta_{pass}}\left(T_{cell}-T\right)$$

where \(T_{cell}\) is the temperature at the center of the surrogate battery and \(\delta_{pass}\) is the distance between the cold-plate measuring point and the battery measuring point. The heat transfer coefficient is then calculated from Newton’s law of cooling as

$$h=\frac{q}{T_w-T_{ref}}$$

where \(T_{ref}\) is the local refrigerant temperature, here approximated as the saturated temperature corresponding to the local pressure of the boiling refrigerant. This data-reduction procedure allows the thermal performance of the EV battery direct-cooling microchannel to be evaluated as a time-resolved curve rather than a single steady-state value.

Comparison of Conventional-Scale and Micro-Scale Channels

In the first part of the experimental campaign, I compared the 3 mm micro-scale cold plate with the 4 mm and 5 mm conventional-scale plates. The purpose was to understand what happens when the channel dimension is reduced from the macro scale to the micro scale under identical compressor speed, expansion-valve opening, and heating-power conditions. Three sets of experiments were performed: variable compressor speed at fixed expansion-valve opening and heating power, variable expansion-valve opening at fixed compressor speed and heating power, and variable electric heating power at fixed compressor speed and expansion-valve opening.

Effect of Compressor Speed

The first set of experiments fixes the expansion-valve opening at 35% and the electric heating power at 50 W, while the compressor speed is changed from 2000 rpm to 3500 rpm in steps of 250 rpm. Raising the compressor speed accelerates the refrigerant circulation, increases the mass flux through the microchannels, and lowers the evaporation pressure, thereby creating a larger temperature difference between the wall and the refrigerant. As a result, the surrogate EV battery cools faster and reaches a lower final temperature. The dynamic measurements show that, at the maximum compressor speed of 3500 rpm, the 3 mm microchannel plate can lower the surrogate battery temperature to about −2.8 °C, whereas the 4 mm and 5 mm conventional plates reach only −1.0 °C and 1.5 °C respectively. At the minimum compressor speed of 2000 rpm, the corresponding terminal temperatures are 1.3 °C, 2.7 °C, and 4.0 °C. These results indicate that the micro-scale channel can exploit the increased compressor capacity more effectively: it does not simply maintain a steady temperature but continues extracting heat even when the source temperature has already dropped well below the comfort level.

Table 4 Surrogate battery terminal temperature after 900 s under different compressor speeds; EEV = 35%, heating power = 50 W.
Compressor speed (rpm) 3-mm plate (°C) 4-mm plate (°C) 5-mm plate (°C)
2000 1.3 2.7 4.0
2250 0.4 1.7 3.0
2500 −0.8 0.5 1.8
2750 −1.6 −0.3 1.0
3000 −2.2 −0.9 0.5
3250 −2.5 −1.0 1.0
3500 −2.8 −1.0 1.5

Although the micro-scale channel exhibits a stronger long-term cooling capability, it is not always the quickest in the early transient. In this work, the “cooling response” is characterized by the time required for the surrogate EV battery to be cooled from 40 °C to 20 °C. At 3500 rpm, the 5 mm plate reaches 20 °C after about 201 s, while the 4 mm and 3 mm plates take about 203 s and 207 s respectively. The narrower microchannel therefore has a lower initial cooling rate, which can be explained by its smaller channel opening: during the early phase, the refrigerant that enters the cold plate is still partly gaseous, so the microchannel cannot immediately accommodate a large refrigerant mass flow. This should be considered when designing fast-charging EV battery cooling systems, where a sudden heat pulse must be damped as quickly as possible.

Temperature uniformity is equally important for EV battery lifetime. The maximum temperature difference between the surrogate battery measurement points is presented in figure-like form through the recorded data. At low compressor speeds, all three plates keep the battery surface temperature difference below 5 °C. When the compressor speed exceeds 2500 rpm, the temperature uniformity of the conventional plates degrades strongly, while the 3 mm microchannel plate still satisfies the 5 °C criterion up to roughly 3000 rpm. At even higher speeds, the microchannel plate also produces a larger cold-plate temperature difference, although the absolute level remains lower than that of the wider channels. The wider channel permits the refrigerant to change phase over a longer distance, so the refrigerant temperature at the outlet is significantly higher than that at the inlet; this increases the longitudinal wall-temperature gradient and worsens the temperature uniformity of the EV battery module.

Effect of Expansion-Valve Opening

The second set of experiments fixes the compressor speed at 2500 rpm and the heating power at 50 W while the electronic expansion-valve opening is varied from 5% to 65%. The expansion-valve opening influences the refrigerant mass flow rate and the evaporating pressure in opposite directions. A smaller opening yields a lower evaporation pressure and therefore a lower saturated refrigerant temperature, which is beneficial for heat transfer. A larger opening allows more refrigerant to enter the cold plate, but the evaporation pressure increases and the temperature difference between the wall and refrigerant shrinks. The experimental results show that the lowest valve opening produces the lowest final battery temperature for every cold plate. At 5% opening, the terminal battery temperatures of the 3 mm, 4 mm, and 5 mm plates are −1.4 °C, 0.2 °C, and 1.3 °C, respectively; at 65% opening, the corresponding values are 9.2 °C, 9.8 °C, and 10.7 °C.

For the cooling response, the conventional channel responds more quickly than the microchannel as the expansion-valve opening is changed. At 65% opening, the surrogate battery reaches 20 °C after about 350 s for the 3 mm plate, but only after 321 s for the 4 mm plate and 302 s for the 5 mm plate. This means that the 5 mm conventional channel saves about 48 s compared with the 3 mm microchannel in this particular transient. Therefore, a wider channel with more physical refrigerant storage inside the plate is better able to cope with a sudden load step, but the steady-state ultimate cooling capacity remains lower than that of the microchannel. This is a classic trade-off between transient response and ultimate capability.

Table 5 Time for the surrogate battery to cool from 40 °C to 20 °C when the expansion-valve opening is varied; compressor speed = 2500 rpm, heating power = 50 W.
EEV opening (%) 3-mm plate (s) 4-mm plate (s) 5-mm plate (s)
5 395 376 358
15 380 357 340
25 366 342 326
35 351 331 317
45 348 329 312
55 349 325 307
65 350 321 302

The mass-flux measurements show a consistent trend: the micro-scale channel has a higher mass flux than the conventional channel for a fixed volumetric flow because the flow area is smaller. At an expansion-valve opening of 65%, the average mass fluxes of the 3 mm, 4 mm, and 5 mm plates are approximately 150.4, 146.2, and 143.0 kg m⁻² s⁻¹. The higher mass flux in the microchannel yields a higher heat-transfer coefficient and a lower wall superheat. Consequently, the microchannel is able to reduce the wall temperature of the EV battery cold plate more effectively in quasi-steady operation.

Effect of Heating Power

The third set of experiments fixes the compressor speed at 2500 rpm and the expansion-valve opening at 35%, while the electric heating power is increased from 25 W to 150 W. These tests simulate different EV battery discharge rates or different state-of-charge conditions. When the heating power is small, the direct-cooling system can easily over-cool the battery and drive its temperature below 0 °C. When the heating power is high, the refrigerant must absorb a much larger heat load, and the cooling system takes longer to reduce the battery temperature. In the 150 W tests, the surrogate battery temperature initially continues to increase by about 4–5 °C before the cooling effect becomes dominant. The thermal mass of the cold-plate assembly delays the refrigeration response, so an EV battery thermal management system with direct cooling must account for this initial thermal overshoot when the heat-generation rate changes abruptly.

More importantly, heating power changes the relative advantage of micro-scale versus conventional channels. At high heating power, the 3 mm microchannel exhibits the strongest heat-transfer enhancement. The heat flux remains above 30 kW m⁻² for a very long portion of the transient, whereas the wider channels experience a more rapid decline in heat flux after the boiling peak. At a heating power of 150 W, the maximum heat flux of the 3 mm microchannel reaches about 107.6 kW m⁻², while that of the 5 mm conventional channel is about 98.5 kW m⁻². This gap demonstrates that microchannels are particularly suitable for high-load EV battery operations such as fast charging, aggressive driving, and cabin-cooling-coupled battery-cooling modes.

Effect of Microchannel Width on Direct-Cooling Performance

After comparing the 3 mm reference channel with the 4 mm and 5 mm macro channels, I continued the investigation with two smaller channels of 1 mm and 2 mm width. These two geometries allow the effect of channel miniaturization to be assessed inside the micro-scale regime. The same operating-condition matrix was applied so that the results could be compared directly with those of the 3 mm channel.

Performance Under Compressor-Speed Sweeps

With the expansion valve and heating power fixed at 35% and 50 W respectively, the compressor speed was again varied between 2000 and 3500 rpm. The narrowest 1 mm channel produces the lowest terminal EV battery temperature in every compressor-speed condition. At 3500 rpm, the 1 mm plate cools the surrogate battery down to about −4.6 °C; the 2 mm plate reaches about −3.6 °C, and the 3 mm plate about −2.8 °C. At 2000 rpm, the terminal temperatures are about −0.6 °C, 0.4 °C, and 1.3 °C respectively. The channel width reduction thus directly improves the ultimate cooling capability. However, the narrowest channel also needs more time to cool the surrogate battery. In the 3500 rpm tests, the 1 mm channel requires about 211 s to cool the battery to 20 °C, whereas the 2 mm and 3 mm channels need about 210 s and 207 s respectively. This difference becomes larger at low compressor speed: at 2000 rpm, the 1 mm channel requires about 356 s while the 3 mm channel requires only about 324 s.

From a mass-flux viewpoint, the 1 mm channel naturally has the highest mass flux because its cross-sectional area is the smallest. At 3500 rpm, the average mass fluxes of the 1 mm, 2 mm, and 3 mm channels are approximately 152.9, 146.6, and 138.8 kg m⁻² s⁻¹. The high mass flux is accompanied by a very thin thermal boundary layer and a thin liquid film on the channel wall. The direct consequence is a very high wall heat-transfer coefficient. In the maximum compressor-speed experiment, the 1 mm channel reaches a heat transfer coefficient of up to 72.14 kW m⁻² K⁻¹, which is much higher than the value of 51.09 kW m⁻² K⁻¹ observed for the 3 mm channel in the same experimental campaign. This result strongly supports the argument that microchannel miniaturization is an effective way to enhance the direct-cooling performance of an EV battery thermal-management system.

Table 6 Selected performance results for microchannels with different widths under varying compressor speed.
Channel width Max. mass flux range (kg m⁻² s⁻¹) Peak heat flux range (kW m⁻²) Peak heat-transfer coefficient (kW m⁻² K⁻¹)
1 mm 136–153 95–152 72.14
2 mm 130–147 90–145 —
3 mm 125–139 85–130 51.09

Temperature Uniformity of the EV Battery Surrogate

Temperature uniformity is strongly improved by reducing the channel width. In the expansion-valve-opening experiments, the 1 mm and 2 mm channels keep the maximum surrogate-battery temperature difference below 5 °C throughout all tested openings from 5% to 65%. The 3 mm channel satisfies this criterion only for larger valve openings. When the compressor speed is increased, the narrower channels remain more uniform than wider channels. At a compressor speed of 3500 rpm, the 1 mm channel has a maximum cold-plate temperature difference of about 20 °C and a battery temperature difference of about 5.9 °C; although this is larger than at low speed, it is still lower than the corresponding value of the 5 mm channel, whose cold-plate temperature difference reaches around 20.5 °C at 2750 rpm. The physical reason is that a narrow channel prevents the refrigerant from stratifying over a long distance. In a narrow channel, the liquid refrigerant occupies most of the cross section and moves at a relatively uniform velocity, so the local evaporation-temperature drop from inlet to outlet is reduced. This makes the surface temperature of the EV battery cold plate much more homogeneous.

Effect of Heating-Power Variation

The 1 mm and 2 mm channels also exhibit a strong response to a change in heating power. When the heating power is increased, the heat flux and heat-transfer coefficient initially increase rapidly because the large wall superheat triggers strong nucleate boiling. The peak heat-flux time is moved sharply toward the beginning of the test. In the 1 mm channel, the time at which the peak heat flux occurs is about 396 s for 25 W heating power, but only about 159 s for 150 W heating power. Thus, the higher heat-generation rate of the EV battery accelerates the development of fully developed boiling. In terms of terminal temperature, the 1 mm channel cools the surrogate battery to about −3.6 °C at 25 W, while the 3 mm channel reaches only about −2.5 °C. At 150 W, the corresponding terminal temperatures are about 10.3 °C and 11.2 °C. Again, the narrowest microchannel provides the lowest steady-state temperature and therefore the largest thermal safety margin for EV batteries.

Flow-Pattern Comparison among Microchannels of Different Widths

One of the key contributions of this work is the visual observation of the boiling flow in transparent microchannels. The flow patterns are not the same for all channel widths. In the 5 mm conventional channel, the refrigerant successively displays annular flow, bubbly flow, and stratified flow. Because the channel is relatively wide, bubbles have enough space to grow without being strongly squeezed by the opposite wall. In the 4 mm channel, the transition processes are similar, but the annular-flow stage persists longer and the bubbles tend to be more uniformly distributed. In the 3 mm microchannel, the narrow space changes the bubble dynamics considerably. The bubbles become denser, they coalesce more easily, and a froth-like flow is regularly observed after the peak of boiling. In the 2 mm channel, the most representative flow pattern is churn flow, where a highly disturbed gas–liquid interface is formed because the large bubbles agitate the liquid film and do not leave enough room for a stable liquid layer. In the 1 mm channel, the bubbles are forced to elongate along the flow direction, producing slug flow and plug flow regimes. In all narrow microchannels, the passage of an elongated bubble is followed by a liquid plug; the thin liquid film between the bubble and the heated wall is extremely important because it controls the local evaporation rate.

Table 7 Dominant two-phase flow patterns observed in the transparent direct-cooling test section for different channel widths.
Channel width Main flow regimes in chronological order Distinct micro-scale feature
5 mm Annular flow → bubbly flow → stratified flow Large stable bubbles; smooth phase separation
4 mm Annular flow → bubbly flow → stratified flow Bubble coalescence at the annular-flow front
3 mm Annular flow → bubbly flow → froth flow → wavy stratified flow High bubble density; frequent bubble breakup and coalescence
2 mm Bubbly-annular flow → churn flow → stratified flow Strongly agitated gas–liquid interface
1 mm Annular flow → slug flow → plug flow → stratified flow Elongated bubbles; alternating liquid slugs and gas plugs

These observations reveal that the channel miniaturization changes not only the bubble size and velocity but also the whole evaporation mechanism. In conventional channels, the heat transfer is dominated by convective boiling where the liquid film flows along the wall and vaporizes at the liquid–vapor interface. In narrow microchannels, the nucleate-boiling contribution becomes stronger because the vapor bubbles occupy a large fraction of the channel cross-section and strongly agitate the liquid film. The confined channel promotes more frequent bubble departure from nucleation sites, leading to thinner liquid films and a smaller thermal resistance across the film. Consequently, the heat-transfer coefficient is enhanced. At the same time, the flow-pattern transition from one regime to another is accelerated, so the microchannel plate reaches the fully developed boiling state earlier than the macro channel when the load is high.

Coupling Between Boiling Pattern and Heat-Transfer Performance

The time-resolved measurements allow me to couple the visual flow pattern with the thermal data. A representative test at 3500 rpm, 35% expansion-valve opening, and 50 W heating power is used here to explain the relationship. During the first tens of seconds, the refrigerant enters the plate as a single-phase vapor or a mixture of vapor and fine mist. The heat-transfer coefficient is still low because only sensible heat exchange occurs. After the liquid refrigerant appears along the channel walls, the flow pattern changes to annular flow. At that moment, the heat flux starts to increase very rapidly because evaporation of the thin liquid film provides a large latent-heat contribution. In the 1 mm channel, the annular-flow period starts later than in the 3 mm channel but is followed by a strong slug-flow period during which the heat-transfer coefficient continues to rise. The highest heat-transfer coefficient is usually obtained in the bubbly or slug/plug transition regime. Once the boiling intensity decreases and a smooth stratified flow is formed, the heat flux stabilizes and then slowly decreases, while the heat-transfer coefficient can continue increasing because the refrigerant saturation temperature itself drops further during the later phase of the experiment.

Table 8 Relation between the two-phase flow regime and the heat-transfer performance of the microchannel direct-cooling plate.
Flow regime Heat-flux behaviour Heat-transfer coefficient behaviour Physical mechanism
Vapor/mist flow Low and slowly rising Low and slowly rising Single-phase sensible heating of gas
Annular flow Rapidly rising; often reaches high level Rapidly rising Evaporation of thin liquid film on the wall
Bubbly/slug/foamy flow Peak is often reached in the early part; then gradual decrease Reaches its maximum at the mid/late stage Intense nucleate boiling; bubble-induced liquid-film thinning
Stratified/wavy flow Stabilizes at a low or moderate level Can still rise if the refrigerant becomes colder Mild evaporation; no intense bubble activity

This coupling mechanism has a direct consequence for EV battery direct-cooling design. If the battery heat-generation rate is high, the cold plate should be designed in such a way that the refrigerant quickly reaches the annular and bubbly-flow stages and maintains these stages for a long time. The experiments show that microchannels with a width of 1–2 mm are more effective in this respect than wider channels. On the other hand, if the EV battery is only lightly loaded, a wider channel may be preferred because it permits a faster cooling response at the beginning of the cooling process. A practical thermal-management strategy could therefore use a combined channel layout: narrow channels in regions where the battery pack generates high heat flux, and wider channels in regions where the heat-generation rate is lower and a quick transient response is desired. Alternatively, the expansion-valve opening and compressor speed can be adjusted so that the refrigerant flow pattern inside a single microchannel geometry is shifted toward the optimal annular/slug-flow regime.

Discussion and Engineering Implications

The results presented above contain several important lessons for designers of EV battery thermal-management systems. First, the hydraulic diameter threshold of 3 mm is not merely a classification boundary; it also marks a transition in boiling dynamics. The 3 mm channel already develops a visibly different bubble regime from the 4 mm and 5 mm channels. Bubbles generated in a 4 mm channel have a large vertical space in which to grow and can easily detach before they touch the opposite side of the channel. In a 3 mm channel, bubble growth is often constrained by the wall, and the bubble must either accelerate along the flow or coalesce with adjacent bubbles. This forced interaction is responsible for the observed improvement in heat-transfer coefficient. As the channel is reduced further to 2 mm and 1 mm, the bubble confinement becomes even stronger, and the annular/slug film-thinning mechanism dominates. The result is an increasingly large wall heat-transfer coefficient and lower battery temperature, but also an increasingly high pressure drop. The pressure-drop penalty was not the focus of this paper, but it may become the limiting factor for very narrow channels.

Second, the dynamic behavior of the cold plate cannot be predicted from steady-state correlations alone. In the early stage of a direct-cooling transient, the compressor must first increase the refrigerant circulation rate and the condenser must first accumulate a sufficient liquid reservoir. During this period, the cold plate is fed with a mixture of vapor and liquid whose quality changes with time. The experiments indicate that conventional wider channels have an advantage in this early phase because they can store a larger amount of refrigerant inside the plate and can therefore supply evaporation heat even before the compressor reaches its full effect. Once the refrigerant circulation becomes fully established, the narrower microchannels overtake the wider ones in cooling capability. For EV application, the control system should therefore account for the thermal inertia of the cold plate and the refrigerant circuit: a brief over-boost of the compressor during the first minute may be needed to initialize the annular flow faster in the microchannel plate, whereas a conventional plate may not require such an aggressive compressor action.

Third, the temperature-uniformity data reveal that the refrigerant-side flow distribution is closely coupled to the channel width. The large difference between the inlet and outlet temperature of the cold plate is mainly caused by the progressive evaporation of the refrigerant along the flow path. In a wider channel, the liquid refrigerant can accumulate on the lower part of the channel while the vapor flows above it, which creates a stratified thermal boundary condition and a large wall-temperature gradient. In a microchannel, the surface tension and the intermittent passage of liquid slugs re-distribute the liquid phase more uniformly. Thus, the EV battery cold plate with 1 mm and 2 mm channels can maintain the cell temperature difference below 5 °C across a wider range of operating conditions. This is especially valuable for battery packs that require long-term operation at high C-rates, where temperature uniformity is closely linked with capacity fade and ageing.

A further important aspect is the way the heating power influences the boiling pattern. When the EV battery heat-generation rate is low, the wall superheat is insufficient to maintain nucleate boiling over the entire plate. The flow pattern changes from annular flow to stratified flow relatively quickly, and the terminal battery temperature is governed by the refrigerant saturation temperature. When the heat-generation rate is high, the boiling remains vigorous for a much longer time, and the heat flux is sustained at high levels. The experiments show that a high heating power accelerates the passage through the early single-phase regime and stabilizes the two-phase boiling regime. This also suggests that a cold plate designed for maximal steady-state performance may not be the optimal choice for a very low-load condition, because the refrigerant temperature might drop below the battery target and require reheating. Thus, the system-level control strategy must be tailored to the EV battery operating state rather than simply maximizing the heat-transfer coefficient.

Finally, the visualization results emphasize that flow pattern is a useful key performance indicator in direct-cooling experiments. Instead of relying only on averaged heat-transfer coefficients, engineers can observe the actual flow regime and determine whether the plate is operating in the desirable annular/slug-flow window. For instance, if a high-speed camera or a micro-electronic phase sensor detects a transition from slug flow to persistent stratified flow, this could indicate that the expansion valve should be closed slightly or the compressor speed should be increased in order to restore a thinner liquid film and more intense boiling. In future EV battery cooling systems, such flow-pattern-based feedback could be combined with model-predictive control to achieve both fast cooling and good temperature uniformity.

Conclusions

This work investigated the micro-scale structure of a direct-refrigerant cold plate for EV battery thermal management. Using a transparent experimental platform, I performed dynamic tests with five cold-plate configurations whose channel widths ranged from 1 mm to 5 mm while all other geometric parameters remained unchanged. The following conclusions can be drawn.

First, replacing a conventional-scale channel with a micro-scale channel of 3 mm hydraulic diameter improves the mass flux, the maximum heat flux, the heat-transfer coefficient, the lowest achievable EV battery temperature, and the temperature uniformity. The 3 mm microchannel kept the heat-transfer coefficient above 30 kW m⁻² K⁻¹ for a long period under high heating power and reached a maximum heat-transfer coefficient of approximately 51.09 kW m⁻² K⁻¹ at the highest compressor speed. In contrast, the conventional 4 mm and 5 mm channels exhibited a faster cooling response in the early transient and therefore shortened the cooling time by as much as 48 s when the expansion-valve opening was changed.

Second, the channel miniaturization beyond 3 mm is beneficial when the primary objective is high heat-flux removal. The 1 mm and 2 mm microchannels produced lower terminal battery temperatures and better temperature uniformity for nearly all operating conditions investigated here. In the maximum compressor-speed test, the 1 mm channel achieved a heat flux of about 152.31 kW m⁻² and a heat-transfer coefficient of 72.14 kW m⁻² K⁻¹. However, the narrower channels required a slightly longer time to cool the EV battery surrogate from 40 °C to 20 °C in the early transient, so the choice of channel width should be made according to the expected load profile and the cooling-control strategy.

Third, the flow-pattern observations provide a direct explanation for the thermal measurement results. Wide channels allow the bubbles to grow freely, resulting in annular, bubbly, stratified, and occasionally churn flow patterns. Narrow microchannels confine the bubbles, creating elongated slug flows, plug flows, and froth flows. The thin liquid film between the elongated bubbles and the channel wall promotes evaporation and greatly reduces the thermal resistance. The heat flux rises rapidly when annular flow first appears, while the heat-transfer coefficient reaches its maximum during the highly agitated bubble-transition regimes. When the flow finally becomes stably stratified, the heat flux tends to level off, but the heat-transfer coefficient can continue to rise as long as the refrigerant saturation temperature decreases further.

In summary, microchannel direct-cooling plates offer a powerful solution for high-performance EV battery thermal management. A well-selected microchannel width between 1 mm and 3 mm provides a good balance among heat-transfer enhancement, temperature uniformity, transient response, cost, and manufacturability. The optimal width depends on the specific EV application, the charging/discharging profile, and the acceptable pressure-drop penalty. Future work should focus on extending the experimental database to larger cold plates with multiple parallel channels, incorporating machine-learning models that can predict the boiling regime in real time, and integrating flow-pattern feedback into the vehicle thermal-management controller so that the direct-cooling system can adapt dynamically to the thermal state of the EV battery pack.